46004
GE Consumer & Industrial Power Protection
GE Consumer & Industrial Power Protection
Power Protection (formerly GE Power Controls), a division of GE Consumer & Industrial, is a first class European supplier of low-voltage products including wiring devices, residential and industrial electrical distribution components, automation products, enclosures and switchboards. Demand for the company’s products comes from wholesalers, installers, -board builders, contractors, OEMs and utilities worldwide.
@
www.ge.com/eu/powerprotection www.ge.com/ex/powerprotection
New GE CONSUMER & INDUSTRIAL HUNGARY Váci út 77 H-1340 Budapest Hungary Customer Service Tel. + 361 447 6046 Fax + 361 447 5060 e-mail: mea.export
[email protected]
GE POWER CONTROLS IBERICA P.I. Clot del Tufau, s/n E-08295 Sant Vicenç de Castellet Spain
GE CONSUMER & INDUSTRIAL GmbH Vor den Siebenburgen 2 D-50676 Köln
GE POWER CONTROLS ITALIA Viale Brianza 181 I-20092 Cinisello Balsamo (MI) Italia
GE INDUSTRIAL BELGIUM Nieuwevaart 51 B-9000 Gent Belgium
GE POWER CONTROLS Paris Nord 2 13, rue de la Perdrix F-95958 Roissy CDG Cédex
GE CONSUMER & INDUSTRIAL POWER PROTECTION Kuortaneenkatu 2 00510 Helsinki Finland
GE imagination at work
SecoGear
12-24kV Metal-clad Switchgear
GE imagination at work 680878 Ref. I/3256/E/EX 3.0 Ed.01/09 © Copyright GE Power Controls 2009
™
SecoGear™
General
SecoGear switchgear is typically used in power plant, substation of public utilities and suitable to provide control and protection for transformers, capacitors and motors. The rated voltage of SecoGear is 12-24kV and rated current ranges from 630A to 4000A. All SecoGear with switching device are equipped with SecoVac vacuum circuit breaker with corresponding specifications. SecoGear switchgear is designed for indoor applications.
12-24kV Metal-clad Switchgear Metal-clad Switchgear
SecoGear metal-clad switchgear is designed and manufactured with advance technology and has been comprehensively and successfully type-tested.
• SecoGear is an air insulated switchgear with a compact design • SecoGear is a safe and reliable switchgear for universal indoor applications • SecoGear is designed with full segregation of its breaker compartment and equipped with embedded pole SecoVac vacuum circuit breaker • SecoGear has cable compartments with ample space for ease of power cable connection • SecoGear is equipped with comprehensive safety interlock systems allowing mistakeproof operation • Features on front ensures the easy and safe operation
SecoGear is particularly suitable for application in industrial i.e. iron and steel mill, mining, oil and gas and infrastructure projects i.e. hi-rise building, airport, water treatment, etc. SecoGear is designed, assembled and tested to meet or exceed applicable lEC, DIN VDE, and GB/DL standards. SecoGear is designed for power protection applications in all major industries, including Power Generation, T&D, Oil&Gas, Automotives, Processing Plants, and Commercial Buildings
Index Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Performance features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 SecoVac. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 VT Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Instrument transformers . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Primary schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Internal wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1
SecoGear™ Comprehensive and Reliable Interlocking System
Metal-clad Switchgear
For personnel safety, SecoGear is designed with a number of comprehensive mechanical interlocks. The mechanical interlocks are designed to prevent: • A closed circuit breaker being racked-in to or racked-out from the connect position • A circuit breaker are being closed on other than connect and test position • A circuit breaker being racked-in to the connect position if the secondary socket has not been plugged/connected • Rack-in of the circuit breaker into the connect position or rack-out from connect position if the door of circuit breaker compartment is opened • Closing of earthing switch when circuit breaker is locked in the connect position • Opening of cable compartment door when earthing switch is in the open position • Disconnecting the secondary socket when circuit breaker at the connect position
Arc-proof Tested
Automatic Shutter System
SecoGear enclosure is designed to meet protection degree of IP4X as per IEC 60529. The grounded metal enclosure protects operators from live parts and moving parts inside the switchgear. The enclosure is sealed to eliminate penetration of external objects, which may cause short circuit of the system. The metal-clad design, sturdy door hinges and lock system, enabled SecoGear to successfully internal arcing test in accordance to IEC 62271-200 in all its three primary compartments.
SecoGear metal-clad switchgear is equipped with an automatic grounded metal shutter each for bus and line/load in front of its primary disconnect bushing. When the breaker is in the test or disconnect position, the shutter will automatically close and lock to provide the designed IP protection and preventing operator from mistake-opening the shutters which may cause personnel injury during maintenance.
Safety - Pressure Relief Design All three primary compartments of SecoGear are provided with pressure relief flaps, which will automatically open and guide the pressurised gas to the rear side direction if an internal arc-fault occurs in an affected compartment. The pressure relief protects damage to switchgear components and the risk of injury to personnel, which may endanger an operator or extend the arc-fault effect to the entire switchgear lineup.
2
SecoGear™ High Reliable Components
Metal-clad Switchgear
SecoGear reliability is based on the usage of proven components. All components including the advanced SecoVac embedded pole vacuum circuit breaker, insulating materials, disconnect bushings, inter-unit bushing and instrument transformers have been strictly selected and have been qualified for 40 years lifetime through accelerated thermal aging tests.
Robust Drawout Mechanism SecoGear drawout mechanism is designed to avoid misalignment during racking, therefore overheating of the primary disconnect is prevented. All drawout mechanism is bolted to the enclosure frame with a double bended .
Space Heaters SecoGear offers space heaters at the cable compartment as a standard feature to avoid condensation inside the switchgear due to high humidity. Space heaters should be permanently energized during installation and commissioning period and can be controlled thru humidistat or thermostat after switchgear is in normal operation.
Remote Control Solution • Only for special order • For remote control from a central control room for intelligent switchgear systems, the following functions of SecoGear are provided: • Motorized drawout mechanism for remote connect and test position • Remote opening and closing the switchgear device • Motorised earthing switch
Environmental Conditions SecoGear is equipped with the following components which guarantee successful operations under adverse climatic and environment: • Epoxy resin embedded pole vacuum circuit breaker • Corrugated design of insulators and bushings • Totally enclosed under all operation conditions SecoGear had successfully ed the high altitude application tests up to 2000m above sea level, grade II pollution test, condensation test and salt spray test.
3
SecoGear™
Metal-clad Switchgear
Performance Features
4
Reliability
Safety
• The 3 primary compartments and 1 secondary compartment are completely self contained and segregated from each other which limits the influence between compartments and prevents spreading of an arc-fault between compartments. • SecoGear is equipped with a Quick-action earthing switch type JN(ESW) with short circuit making capability. • A heat-shrinkable material with high dielectric and strength properties insulates the busbar. • The main busbar is provided with inter-unit bushing to prevent travel of arcing to the entire main busbar of the line-up. • SecoGear is equipped with a highly reliable SecoVac vacuum circuit breaker with excellent electrical and mechanical performance. • Circuit breaker in the SecoGear switchgear has three positions: connected, test and disconnected positions.
SecoGear is designed with a number of interlocking systems to prevent maloperation: • The circuit breaker can only be moved from test to connect position and vice versa when circuit breaker is opened. • The earthing switch cannot be closed when the circuit breaker is in the connect position and in the traveling position between test and connect. • The cable compartment door can be opened only when the earthing switch is closed and at the same time the earthing switch can be opened only when the cable compartment door is closed. • The secondary plug can only be inserted or removed only when the circuit breaker is in the test position. • The circuit breaker can only be closed when the circuit breaker is precisely in the definite test or connection position. • When the circuit breaker is removed from connect position, the metal shutters will close automatically. • The switchgear is internally arc-proof. • All high primary compartments are provided with a pressure relief flaps located on the topside of the switchgear. • Any overpressure inside the compartment by an internal arcing will be released thru the pressure relief flaps.
SecoGear™
Adaptability
Performance Features
• SecoGear cable compartment provides ample space for easy power cable connection. • Standard current transformers, zero sequence current transformer, voltage transformers, surge arresters, protection relays and other instruments can be easily installed to the switchgear. • SecoVac vacuum breakers with the same rating are interchangeable without any adjustment. • CNC punching and bending machines ensure high quality and consistent dimensions and weight of the cubicle.
Technical Data of SecoGear Switchgear Description
Unit
Data
Rated voltage Rated frequency
kV Hz
12 50/60
24 50/60
Rated power frequency stand voltage/1 minute Lightning impulse with stand voltage (peak value)
kV kV
42 75
65 125
Rated current of busbar Rated current of T-off Busbar Rated short time withstand current (3s)
A A kA
Rated peak withstand current (peak value) Resistance of main circuit
kA μΩ
630/1250/1600/2000/2500/3150/4000(1) 630/1250/1600/2000/2500/3150/4000(1) 20/25/31.5/40/50 ≤ 150+CT(2)(≤ 630A) 50/63/80/100/125 ≤ 100+CT(2)(≤ 1250A) ≤ 70+CT(2)(≤ 2000A) ≤ 50+CT(2)(≤ 2500A) IP4X, Compartment IP2X
630/1250/1600/2000/2500 630/1250/1600/2000/2500 20/25/31.5 ≤ 150+CT(2)(≤ 630A) 50/63/80 ≤ 100+CT(2)(≤ 1250A) ≤ 70+CT(2)(≤ 2000A) ≤ 50+CT(2)(≤ 2500A) IP4X, Compartment IP2X
Ingress protection (1) Forced cooling ventilation is required (2) Direct current resistance of current transformer
Normal Service Conditions Description Minimum ambient temperature Maximum ambient temperature Daily average temperature Maximum relative humidity Monthly average relative humidity Maximum altitude
-15°C +40°C ≤+35°C 95% ≤90% 2000m a.s.l.
5
SecoGear™ Dimensions and Weight 12kV
Height (h) (mm)
Metal-clad Switchgear
T-off busbar rated current ≤ 1250A Short time withstand current ≤ 31.5kA T-off busbar rated 1250A Short time withstand current = 40kA/50kA T-off busbar rated current = 1600A/2000A T-off busbar rated current ≥ 2500A
Width (w) (mm)
Depth (d) (mm)
Mass (kg)
1400
800-1200
1680
800-1200
650/800
2250
800/1000 800/1000 1000
24kV T-off busbar rated current ≤ 1250A Short time withstand current ≤ 25kA 1250A < T-off busbar rated current ≤ 2500A 25kA < Short time withstand current ≤ 31.5kA
2250
800 or 1000 (Choice or better optional) 1000
SecoGear front and cross section view Front view
A = Busbar compartment B = Circuit breaker compartment C = Cable compartment D = Low Voltage compartment
6
Side view
SecoGear™
SecoVac Medium voltage embedded pole vacuum circuit breaker 12-24kV, up to 4000A and 50kA
Description Rated voltage Rated frequency Rated power frequency withstand voltage (1 minute) Rated impulse withstand voltage (peak value) Rated current Rated short circuit breaking current Rated short time withstand current (3 seconds)
SecoVac
• SecoVac satisfies diverse application requirements: its simple but reliable operating mechanism is a key factor to make switchgear compact. • SecoVac is manufactured using specially customized materials and specialized techniques. The process ensures quality and reliability of product. It is suitable for application in different operating conditions. • The modularized operating mechanism design of SecoVac allows for standardized mass production, shorter lead-time, and a fast module replacement to minimize downtime. • SecoVac fully complies with IEC, DIN VDE and GB/DL standards.
Unit
Data
Data
kV Hz kV kV A kA kA
12 50/60 42 75 630/1250/1600/2000/2500/3150/4000 (fan cooled) 20/25/31.5/40/50 20/2/31.5/40/50
24 50/60 65 125 630/1250/1600/2000/2500 20/25/31.5 20/25/31.5
7
SecoGear™ SecoVac technical data Description Rated peak value withstand current Rated short circuit making current (peak value) Electrical endurance Rated short circuit breaking times Rated operating sequence
Metal-clad Switchgear
Rated auxiliary control voltage Closing time Opening time Breaking time Average closing speed Average opening speed Asynchronous time Bouncing time Resistance of main circuit
Distance between poles Mechanical endurance *For other requirement please GE
8
Unit
Data (12 kV)
Depth (d) (mm) (24kV)
kA kA No. of times No. of times
50/63/80/100/125 50/63/80/100/125 274(E2) - IEC62271-100: 2006 50 with ARC: O-0.3s-CO-180s-CO without ARC: O-180s-CO-180s-CO AC110/220; DC110/220 ≤ 60 ≤ 45 ≤ 60 0.5~1.1 1.1~1.7 ≤2 ≤2 ≤ 80 (630A) ≤ 45 (1250A) ≤ 35 (1600~2000A) ≤ 35 (2500A) 150/210/275 30000 (M2)
50/63/80 50/63/80 274(E2) - IEC62271-100: 2006 50 with ARC: O-0.3s-CO-180s-CO without ARC: O-180s-CO-180s-CO AC110/220; DC110/220 ≤ 60 ≤ 45 ≤ 60 0.5~1.1 1.1~1.7 ≤2 ≤2 ≤ 80 (630A) ≤ 45 (1250A) ≤ 35 (1600~2000A) ≤ 35 (2500A) 210/275 20000 (M2)
V ms ms ms m/s m/s ms ms μΩ
mm No. of times cycles
SecoGear™
VT Module There are 2 types of VT modules available on our SecoGear: • Withdrawable VT module with primary fuses for line voltage sensing at the cable compartment of breaker • Withdrawable VT module with primary fuses for bus voltage sensing at metering
VT Module
A special fixed type VT module without primary fuses for bus voltage sensing (mounted on the top of breaker ) is available. This option is intended to eliminate number of vertical sections for dedicated metering . Number of the voltage transformer on the VT module can be 2 or 3 VT depending on the application and requirement. The withdrawable VT module allows replacement of the fuses with the switchgear in service. Truck racking-out with the door closed operates closure of an automatic shutter between the live parts of the switchgear and the VT metering compartment. Surge arresters on a drawn-out VT module and blown fuse indicator switch are as an option.
Voltage Transformer The voltage transformers can be one or two poles type, with performances and accuracy classes suited to the functional requirements of the connected devices. When they are installed on a withdrawable truck they are fitted with primary fuses. The current and voltage transformers are designed to meet or exceed requirement of IEC60044-1 and IEC60044-2 standards respectively.
9
SecoGear™
Instrument Transformer Metal-clad Switchgear
Current Transformer The current transformer and voltage transformer are cast-resin type instrument transformers for measuring devices and protection devices of indoor application at the frequency of 50 or 60Hz. The instrument transformers are moulded in high quality epoxy resin to have a good performance at high polluted and humid area. The instrument transformer is designed to suit installation in tropical environment and it doesn’t need special maintenance. The instrument transformers can be mounted at any position. The lightweight and small dimensions are the main features of its design. The current transformer secondary terminals are located in recesses either in one or both sides of the transformer base, therefore giving two connection possibilities for installation flexibility. A ring type CT is also available for ground protection devices.
10
SecoGear™ Primary schemes of SecoGear Scheme No Primary schemes
Scheme No Primary schemes
Rated current (A) Main Apparatus SecoVac vacuum circuit breaker Current transformer Voltage transformer High voltage fuse Earthing switch Arrester Application
Scheme No Primary schemes
Rated current (A) Main Apparatus SecoVac vacuum circuit breaker Current transformer Voltage transformer High voltage fuse Earthing switch Arrester Application
2
3
4
5
6
630~4000
630~4000
630~4000
630~4000
630~4000
630~4000
1 2 I.F
1 2 1 I.F
1 2 1 3 I.F
1 3 I.F
1 3 1 I.F
1 3 1 3 I.F
7
8
9
10
11
12
630~4000
630~4000
630~4000
630~4000
630~4000
630~4000
1 2 B
1 2 1 B
1 2 B
1 2 1 B
1 3 B
1 3 1 B
13
14
15
16
17
18
630~4000
630~4000
630~4000
630~4000
630~4000
630~4000
1 3 B
1 3 1 B
1 2 B
1 2 1 B
1 2 B
1 2 1 B
Primary schemes
Rated current (A) Main Apparatus SecoVac vacuum circuit breaker Current transformer Voltage transformer High voltage fuse Earthing switch Arrester Application
1
11
SecoGear™ Primary schemes of SecoGear (continued)
Metal-clad Switchgear
Scheme No Primary schemes
Rated current (A) Main Apparatus SecoVac vacuum circuit breaker Current transformer Voltage transformer High voltage fuse Earthing switch Arrester Application
Scheme No Primary schemes
Rated current (A) Main Apparatus SecoVac vacuum circuit breaker Current transformer Voltage transformer High voltage fuse Earthing switch Arrester Application
Scheme No Primary schemes
Rated current (A) Main Apparatus SecoVac vacuum circuit breaker Current transformer Voltage transformer High voltage fuse Earthing switch Arrester Application
12
19
20
21
22
23
24
630~4000
630~4000
630~4000
630~4000
630~4000
630~4000
1 3 B
1 3 1 B
1 3 B
1 3 1 B
1 2 I.F
1 2 1 I.F
25
26
27
28
29
30
630~4000
630~4000
630~4000
630~4000
630~4000
630~4000
1 2 1 3 I.F
1 3 I.F
1 3 1 I.F
1 3 1 3 I.F
1 2 2 3 I+P
1 2 2 3 1 I+P
31
32
33
34
35
36
630~4000
630~4000
630~4000
630~4000
630~4000
630~4000
1 2 2 3 3 I+P
1 3 2 3 I+P
1 3 2 3 1 I+P
1 3 2 3 3 I+P
1 2 3 3 I+P
1 2 3 3 1 I+P
SecoGear™ Primary schemes of SecoGear (continued) Scheme No Primary schemes
Scheme No Primary schemes
Rated current (A) Main Apparatus SecoVac vacuum circuit breaker Current transformer Voltage Transformer High voltage fuse Earthing switch Arrester Application
Scheme No Primary schemes
Rated current (A) Main Apparatus SecoVac vacuum circuit breaker Current transformer Voltage transformer High voltage fuse Earthing switch Arrester Application
38
39
40
41
42
630~4000
630~4000
630~4000
630~4000
630~4000
630~4000
1 2 3 3 3 I+P
2 3 P
3 3 P
2 3 3 P+Arrester
3 3 3 P+Arrester
2 3 3 P+Arrester
43
44
45
46
47
48
630~4000
630~4000
630~4000
630~4000
630~4000
630~4000
3 3 3 P+Arrester
2 3 P+R
2 3 P+R
3 3 P+R
3 3 P+R
2 3 3 P+R +Arrester
49
50
51
52
53
54
630~4000
630~4000
630~4000
630~4000
630~4000
630~4000
2 3 3 R+P+Arrester
3 3 3 R+P+Arrester
3 3 3 R+P+Arrester
R
R
D
Primary schemes
Rated current (A) Main Apparatus SecoVac vacuum circuit breaker Current transformer Voltage transformer High voltage fuse Earthing switch Arrester Application
37
13
SecoGear™ Primary schemes of SecoGear (continued)
Metal-clad Switchgear
Scheme No Primary schemes
Rated current (A) Main Apparatus SecoVac vacuum circuit breaker Current transformer Voltage transformer High voltage fuse Earthing switch Arrester Application
Scheme No Primary schemes
Rated current (A) Main Apparatus SecoVac vacuum circuit breaker Current transformer Voltage transformer High voltage fuse Earthing switch Arrester Application
Scheme No Primary schemes
Rated current (A) Main Apparatus SecoVac vacuum circuit breaker Current transformer Voltage transformer High voltage fuse Earthing switch Arrester Application
14
55
56
57
58
59
60
630~4000
630~4000
630~4000
630~4000
630~4000
630~4000
D+B
D+B
2 3 D+B+P
2 3 D+B+P
-
1 -
61
62
63
64
65
66
630~4000
630~4000
630~4000
630~4000
630~4000
630~4000
2 2 3 M
2 2 3 M
3 2 3 M
3 2 3 M
2 3 3 M
2 3 3 M
67
68
69
70
71
72
630~4000
630~4000
630~4000
630~4000
630~4000
630~4000
3 3 3 M
3 3 3 M
1 2 2 3 I+M
1 2 2 3 I+M
2 2 3 I+M
2 2 3 I+M
Outgoing phase changing Outgoing phase changing
SecoGear™ Primary schemes of SecoGear (continued) Scheme No Primary schemes
74
75
76
77
78
630~4000
630~4000
630~4000
630~4000
630~4000
630~4000
1 3 2 3 I+M
1 3 2 3 I+M
3 2 3 3 I+M
3 2 3 I+M
Transformerx1 3 3 T
Capacitorx3 3 3 Compensation
Meaning of code name in primary schemes: B = Coupling D = Disconnecting F = Outgoing I = Incoming M = Metering P = PT R = Busbar rising T = T
Primary schemes
Rated current (A) Main Apparatus SecoVac vacuum circuit breaker Current transformer Voltage transformer High voltage fuse Earthing switch Arrester Application
73
Examples of the scheme application Example 1
Example 2
05
01
64
41
50
02
011
02
55
02
01
41
01
15
SecoGear™ Internal Wiring Diagrams Withdrawable Type – AC Control
2nd opening circuit
Metal-clad Switchgear
Opening circuit
Close blocking circuit
Over Over Over Under current current current current release release release release Charging circuit (A phase) (B phase) (C phase)
Closing circuit
Truck Rack Block magnet
Closing monitor circuit
Y0
Blocking Magnet for withdrawable unit-- V0 Y1 Closing block magnet Y2 First opening release Y3 Closing release Y4 Undervoltage release Y7-Y9 Indirect overcurrent release (optional) Y10 Second opening release (optional) P Manual charging M Charging motor V0-V5 Rectifier (V0&V5 optional)
S1 S2 S3 S8 S9 K0 R0 JP1 JS1
Auxiliary switch of charging Motor Auxiliary switch of block magnet-Y1 Auxiliary switch of VCB Auxiliary switch for test position Auxiliary switch for service position Anti-pumping relay Resistance By of R0 Connector of K0 (the internal antipumping function will be dismissed if it is cut)
Notes: 1. Auxiliary switch-S1 shown for VCB-mechanism is discharged. 2. VCB in opening and service status. 3. The optional components are not included in basic version if not specified.
Service position Test position
Withdrawable Type – DC Control
Opening circuit
2nd opening circuit
Close blocking circuit
Closing circuit
Truck Rack Block magnet
Charging circuit
Closing monitor circuit
Y0
Blocking Magnet for withdrawable unit-- V0 Y1 Closing block magnet Y2 First opening release Y3 Closing release Y4 Undervoltage release Y7-Y9 Indirect overcurrent release (optional) Y10 Second opening release (optional) P Manual charging M Charging motor
Service position Test position
16
Over Over Over Under current current current current release release release release (A phase) (B phase) (C phase)
S1 S2 S3 S8 S9 K0 R0 JP1 JS1
Auxiliary switch of charging Motor Auxiliary switch of block magnet-Y1 Auxiliary switch of VCB Auxiliary switch for test position Auxiliary switch for service position Anti-pumping relay Resistance By of R0 Connector of K0 (the internal antipumping function will be dismissed if it is cut)
Notes: 1. Auxiliary switch-S1 shown for c.b.-mechanism discharged. 2. VCB in opening and service status. 3. The optional components are not included in basic version if not specified.
SecoGear™
Fixed Type – AC Control
2nd opening circuit
Close blocking circuit
Closing circuit
Internal Wiring Diagrams
Opening circuit
Over Over Over Under current current current current release release release release Charging circuit (A phase) (B phase) (C phase)
Closing monitor circuit
Notes: 1. Auxiliary switch-S1 shown for VCB-mechanism is discharged. 2. VCB in opening status. 3. The optional components are not included in basic version if not specified. 4. Auxiliary switch S2 should be byed when block magnet Y1 is not required.
Y1 Y2 Y3 Y4 Y7-Y9 Y10 P M V0-V5
Closing block magnet First opening release Closing release Undervoltage release Indirect overcurrent release (optional) Second opening release (optional) Manual charging Charging motor Rectifier (V0&V5 optional)
S1 S2 S3 K0 R0 JP1 JS1
Auxiliary switch of charging Motor Auxiliary switch of block magnet-Y1 Auxiliary switch of VCB Anti-pumping relay Resistance By of R0 Connector of K0 (the internal antipumping function will be dismissed if it is cut)
Fixed Type – DC Control
Opening circuit
2nd opening circuit
Close blocking circuit
Over Over Over Under current current current current release release release release Charging circuit (A phase) (B phase) (C phase)
Closing circuit
Closing monitor circuit
Notes: 1. Auxiliary switch-S1 shown for VCB-mechanism is discharged. 2. VCB in opening status. 3. The optional components are not included in basic version if not specified. 4. Auxiliary switch S2 should be byed when block magnet Y1 is not required. 5. The connect points in dashed are as should be connected with positive pole.
Y1 Y2 Y3 Y4 Y7-Y9 Y10 P M
Closing block magnet First opening release Closing release Undervoltage release Indirect overcurrent release (optional) Second opening release (optional) Manual charging Charging motor
S1 S2 S3 K0 R0 JP1 JS1
Auxiliary switch of charging Motor Auxiliary switch of block magnet-Y1 Auxiliary switch of VCB Anti-pumping relay Resistance By of R0 Connector of K0 (the internal antipumping function will be dismissed if it is cut)
17
SecoGear™
Metal-clad Switchgear
Installation of switchgear In order to obtain an optimum installation sequence and ensure high quality standards, site installation of the switchgear should only be carried out by specially trained, or at least by personnel supervised and monitored by responsible persons. On commencement of installation on site, the switchroom must be fundamentally finished, provided with lighting and the electricity supply, lockable, dry and with facilities for ventilation. It is also required that Figure 1: plane layout for switchgear arrangement
Figure 2: plane layout for switchgear arrangement (section A-A)
18
the basic frame and indoor ground of switch should be checked and accepted before the construction. It must be ensured that the ceiling height is sufficient for the opening travel of the pressure relief plates. Tolerances for laying the floor frame are: Evenness tolerance: ± 1mm within a measuring length of 1m. Straightness tolerance: 1mm per 1m, but not more than 3mm over entire length of frame.
SecoGear™
Figure 3: Switch-room cable duct arrangement
Installation
Figure 4: Typical basic frame foundation (for 1000 mm/800 mm width dimension model)
19
SecoGear™
Metal-clad Switchgear
Notes
20
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
46004
GE Consumer & Industrial Power Protection
GE Consumer & Industrial Power Protection
Power Protection (formerly GE Power Controls), a division of GE Consumer & Industrial, is a first class European supplier of low-voltage products including wiring devices, residential and industrial electrical distribution components, automation products, enclosures and switchboards. Demand for the company’s products comes from wholesalers, installers, -board builders, contractors, OEMs and utilities worldwide.
@
www.ge.com/ex/powerprotection www.ge.com/eu/powerprotection
GE POWER CONTROLS IBERICA P.I. Clot del Tufau, s/n E-08295 Sant Vicenç de Castellet Spain GE POWER CONTROLS ITALIA Viale Brianza 181 I-20092 Cinisello Balsamo (MI) Italia
GE CONSUMER & INDUSTRIAL HUNGARY Váci út 77 H-1340 Budapest Hungary Customer Service Tel. + 361 447 6046 Fax + 361 447 5060 e-mail: mea.export
[email protected]
GE CONSUMER & INDUSTRIAL 1101, City Tower 2, Sheikh Zayed Road P.O. Box 11549, Dubai United Arab Emirates Tel. +97143131202 GE CONSUMER & INDUSTRIAL Naberezhnaya Tower, Krasnopresnenskaya nab., 18, 11 floor Moscow 123317 Russia Tel. +74957396856 GE CONSUMER & INDUSTRIAL Unit 4, 130 Gazelle Avenue Corporate Park Midrand 1685 PO Box 76672 Wendywood 2144 South Africa Tel. +2711 238 3000
GE POWER CONTROLS Paris Nord 2 13, rue de la Perdrix F-95958 Roissy CDG Cédex GE CONSUMER & INDUSTRIAL Vor den Siebenburgen 2 D-50676 Köln GE INDUSTRIAL BELGIUM Nieuwevaart 51 B-9000 Gent Belgium
New
SecoGear
12-24kV Metal-clad Switchgear
GE CONSUMER & INDUSTRIAL Kuortaneenkatu 2 00510 Helsinki Finland
GE imagination at work
GE imagination at work 680878 Ref. I/3256/E/EX 3.0 Ed.01/09 © Copyright GE Power Controls 2009
™